Back

GigaLine® KL-U-D(ZN)BH CI Dca
Universal cable, with circuit integrity 90 min., 2500 N
1 x 12 G50/125/250 OM3

3D_GL_U-DQ(ZN)BH_CI_zent_SM_GE.png

Properties / Applications

Properties: Universal cable with CI 90 min for fixed installation.
Circuit integrity test acc. to IEC 60331-11 / IEC 60331-25 (750°C, 90 min)
max. change of attenuation 2.0 dB
(VDE test report 111100-9020-0001/11291)
Resistance to fire for use in emergency circuits test acc. to EN 50200:2015 (830 +40/ -0°C, 180 min)
max. change of attenuation
Multi Mode
max. 2.0 dB at 850 nm and 1300 nm
(VDE test reports:
5005019-9601-0001/249341-TL6-2
Date: 2018-07-20
5005019-9601-0001/257978-TL6-2
Date: 2019-12-20)

Application: Suitable for campus/ backbone cabling and for the use in generic cabling acc. to ISO/IEC 11801 and EN 50173. Ideally suited for all applications of Classes OF 300 to OF 10000 (depending on the fiber). Building entries without additional transition points (splices) possible.

Description

Fibre optic universal cable with central jelly filled loose tube, with non-metallic rodent protection and CI. Inner fire barrier. Fire protection tape made of woven glass. The cable is completely metal-free and non-conductive (dielectric).

Product information

Part number: LKD8UA500B60000

Application: DataCenter Office

Category: OM3

Fire class: Dca -s2,d2,a1

DoP: CDESK0000082

Number of fibres: 12

Technical information

Bending radius (static) (min.): 15x outer-Ø

Bending radius (dynamic) (min.): 20x outer-Ø

Transport / storage: -25 °C up to + 70 °C

During installation: -5 °C up to +50 °C

After installation: -25 °C up to +60 °C

Flame retardancy: IEC 60332-1-2 IEC 60332-3-22 Cat. A

Halogen-free: IEC 60754-1

Smoke density: IEC 61034-1